Delta Technology (Chongqing) Co., Ltd.

Quality Assurance, Service Priority.

Manufacturer from China
Verified Supplier
2 Years
Home / Products / Electric Testing Equipment /

Oltc High Quality Electrical Testing on Load Tap Changer Tester

Contact Now
Delta Technology (Chongqing) Co., Ltd.
Visit Website
City:chongqing
Province/State:chongqing
Country/Region:china
Contact Person:MsTina Chen
Contact Now

Oltc High Quality Electrical Testing on Load Tap Changer Tester

Ask Latest Price
Video Channel
Brand Name :Delta
Model Number :OLTC
Certification :ISO9001
Place of Origin :China
MOQ :1 set
Price :USD1.0
Payment Terms :Western Union, T/T, L/C
Supply Ability :100 sets each month
Delivery Time :10 days
Packaging Details :OLTC is packed in veneer case
Item Name :Oltc High Quality Electrical Testing on Load Tap Changer Tester
Functions :Automatic Transformer on Load Tap Changer Tester
Features :Transformer on Load Tap Changer Tester
Current Source Charge :3A/1A, 0.6A/0.2A
Power Supply :AC 220V, 50Hz/60Hz
Temperature :-10-40°C
Humidity :<85%RH
Application Field :Electrical Industry, Oil Laboratory, etc.
Delivery Lead Time :7 Days After The Order Is Confirmed
Shipping Method :Suggest to Ship by Air or Express
Protection Functions :Power-off Protection, Over-Voltage Protection
Max. Voltage of The Port :24V
Max. Range of Transition Resistance :100ohm
Measuring Range :1A: 0.4-20ohm, 0.2A: 10-100ohm
Record Time of Waveform :300ms
Sample Rate :30K
OEM Service :Yes, available, for free
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Oltc High-Quality Electrical Testing on Load Tap Changer Tester

Introduction:

  • Oltc High-Quality Electrical Testing on Load Tap Changer Tester can record switch operation waveform in the overall process. The longest time is 6.4s.

  • Oltc High-Quality Electrical Testing on Load Tap Changer Tester can test various parameters such as transition waveform, transition time, transition resistance, and three-phase synchronization one time and analyze results automatically.

  • Oltc High-Quality Electrical Testing on Load Tap Changer Tester has power-off protection, over-voltage protection, perpetual clock, and high-speed printing.

Features:

  • Test transformers of type Y0 Y Δ and display resistance value directly.
  • Automatically analyze waveform faults and mark the fault.
  • Automatically adjust resistance value and time range according to sampling data.
  • Transformer type Δ is able to display to synchronization status of three phases.
  • Be able to test with winding or without winding.
  • Four terminal connection modes provide high accuracy of resistance measurement.
  • Continuous test to save time of power off.
  • Make a word report.
  • 800×480 colorized LCD with touch screen and high-speed printer.
  • Store 1000 groups of data and also can be saved by USB flash disk.

Parameters:

Item Name Oltc High-Quality Electrical Testing on Load Tap Changer Tester
Three-phase constant current source charge Three-phase constant current source charge
Maximum voltage of the port 24V
Maximum range of transition resistance 100Ω
Measuring range 1A: 0.4Ω~20Ω 0.2A: 10Ω~100Ω
Record time of waveform 300ms
Sample rate 30k
Resolution of time 0.1ms
Resolution of resistance 0.1Ω
Accuracy of transition resistance ±5% Reading±0.1Ω
Accuracy of transient time ±0.5% Reading±0.2mS
Temperature -10-40°C
Humidity <85%RH

Oltc High-Quality Electrical Testing on Load Tap Changer Tester ​Real Picture:

Oltc High Quality Electrical Testing on Load Tap Changer TesterOltc High Quality Electrical Testing on Load Tap Changer Tester

Inquiry Cart 0